The RAYCHEM TOUCH1500 is a panel mounted display used in conjunction with RAYCHEM NGC-20 and RAYCHEM NGC-40 Control and Monitoring Systems devices. The RAYCHEM TOUCH1500 is rated IP 65 (NEMA 4) and can be mounted both indoors and outdoors. The RAYCHEM TOUCH1500 kit includes all hardware required for mounting in a suitable electrical panel.

TOUCH 1500R, A remote version of TOUCH1500 is also available as a standalone solution for applications in which the controllers are not in the same location as the user interface.

Make Your Systems Talk!

Now more than ever, open communication systems, data integration, easy configuration and real-time monitoring are critical components of running an industrial installation. With the latest Touch 1500 software, RAYCHEM offers the full data integration of its heat tracing systems with process control systems, allowing for the reduction of maintenance and energy costs and, consequently, increasing process productivity.

RAYCHEM Touch 1500 to DCS means “data a la carte.” The heat tracing data you want, in your preferred format for your DCS system.

Technical Specifications

TOUCH 1500
Area(s) of useNonhazardous locations, indoor or outdoor (Type 4X, IP66)
Operating temperature (CE)*
Touch 1500-HAZ-CPU:
Touch 1500-HAZ-TS:

–20°C to 60°C (–4°F to 140°F)
–20°C to 60°C (–4°F to 140°F)
Storage temperature–30°C to 80°C (–22°F to 176°F)
Dimensions
Touch 1500-HAZ-CPU:
Touch 1500-HAZ-TS:

85.5 x 139 x 152 mm (3.4 x 5.5 x 6 in)
422 x 68 x 338 mm (16.61 x 2.68 x 13.31 in)
Amperage Rating
Touch 1500-HAZ-CPU:
Touch 1500-HAZ-TS:

2 A @ 24 Vdc
2.62 A @ 24 Vdc
Relay outputsOne Form C relay rated at 12 A @ 250 Vac. Relay is used as a common alarm. To be ordered separately
DisplayLCD is a 15-in XGA, colour TFT transflective device with integral LED backlight Touch Screen, 4-wire resistive touch screen interface for user entry
Supply voltage
TOUCH 1500-HAZ-TS
TOUCH 1500-HAZ-TS

10-36 Vdc
19-30 Vdc


TOUCH 1500R
Area(s) of useNonhazardous, Indoors (IP65, NEMA 4)
Supply voltage100 – 240 Vac ±10%, 50/60 Hz
Operating temperature0°C to 50°C
Storage temperature-20°C to 60°C
Dimensions610 mm (W) X 508 mm (H) X 152 mm (D)
Relay outputsOne Form C relay rated at 12 A @ 250 Vac. Relay is used as a common alarm. Relays may be assigned for alarm outputs.
Display15-inch touch screen
Connection and Protection